Information disclosure in Siemens SIMATIC PCS 7 and SIMATIC WinCC web applications

Note: This data is for reference and cybersecurity research purposes only.CyStack advises users not to use this information for unlawful purposes.

What is CVE-2024-30321?

CVE-2024-30321 is a vulnerability classified as Exposure of Private Personal Information to an Unauthorized Actor, affecting SIMATIC PCS 7 V9.1 (affected versions: < V9.1 SP2 UC05), SIMATIC WinCC Runtime Professional V18 (affected versions: < V18 Update 5), SIMATIC WinCC Runtime Professional V19 (affected versions: < V19 Update 2), and 3 more products. This vulnerability is rated High, with a CVSS score of 8.2. Current sources do not report this vulnerability as exploited.

Overview

Original source data

A vulnerability has been identified in SIMATIC PCS 7 V9.1 (All versions < V9.1 SP2 UC05), SIMATIC WinCC Runtime Professional V18 (All versions < V18 Update 5), SIMATIC WinCC Runtime Professional V19 (All versions < V19 Update 2), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 23), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 17), SIMATIC WinCC V8.0 (All versions < V8.0 Update 5). The affected products do not properly handle certain requests to their web application, which may lead to the leak of privileged information. This could allow an unauthenticated remote attacker to retrieve information such as users and passwords.

Affected products and scope

The following ranges are confirmed as affected:

  • Siemens SIMATIC PCS 7 V9.1: all versions < V9.1 SP2 UC05.
  • Siemens SIMATIC WinCC Runtime Professional V18: all versions < V18 Update 5.
  • Siemens SIMATIC WinCC Runtime Professional V19: all versions < V19 Update 2.
  • Siemens SIMATIC WinCC V7.4: all versions < V7.4 SP1 Update 23.
  • Siemens SIMATIC WinCC V7.5: all versions < V7.5 SP2 Update 17.
  • Siemens SIMATIC WinCC V8.0: all versions < V8.0 Update 5.

Branches or configurations not listed here are not determined by this entry to be safe or affected.

Technical details

Siemens identifies the affected components as the WinCC WebNavigator, PCS 7 Web Server, and PCS 7 Web Diagnostics Server web applications. The products improperly handle certain attacker-controlled requests sent to the web application, which may cause privileged information to be returned without successful authentication. The supported reachability is remote over the network, and the attacker does not need privileges or user interaction. The advisory does not disclose the endpoint, request syntax, response format, or specific code path involved. The available evidence therefore does not establish which exact request or configuration is required beyond access to the affected web application.

Exploitability

The vulnerability is reachable over the network when an affected web application can be accessed. Siemens describes the threat as an unauthenticated remote attacker, and the normalized record indicates that no privileges or user interaction are required. The supplied CVSS entries assess attack complexity differently between CVSS versions, so this entry does not reduce that difference to one universally confirmed practical complexity. The supplied record marks public_exploit as false, but it does not establish whether exploitation has occurred in the wild. No public exploit, payload, or specific exploitation indicator is identified in the available sources.

Technical impact

Successful exploitation can disclose privileged information from the web application, including users and passwords. The confirmed impact is to confidentiality; the record does not establish the ability to modify data or disrupt service. If disclosed information remains valid, the organization may need to assess the risk of subsequent access and the scope of related accounts, but reuse of the information is not confirmed. The practical impact depends on where the web service is reachable, which data the response exposes, and whether the disclosed account information remains valid.

Business impact

The primary risk is disclosure of authentication information and account data in process-control or SCADA environments. Exposed users and passwords could increase the risk of subsequent unauthorized access if the credentials remain valid, but the advisory does not confirm that leaked information was used or that an account was compromised. Organizations may need to review access scope, assess affected accounts, and examine web services exposed to untrusted networks. The available evidence confirms a confidentiality impact but does not establish data modification or service disruption.

Remediation

  1. Update each product branch to the corresponding Siemens baseline:
  • SIMATIC PCS 7 V9.1: V9.1 SP2 UC05 or later version as directed by Siemens.
  • SIMATIC WinCC Runtime Professional V18: V18 Update 5 or later version as directed by Siemens.
  • SIMATIC WinCC Runtime Professional V19: V19 Update 2 or later version as directed by Siemens.
  • SIMATIC WinCC V7.4: V7.4 SP1 Update 23 or later version as directed by Siemens.
  • SIMATIC WinCC V7.5: V7.5 SP2 Update 17 or later version as directed by Siemens.
  • SIMATIC WinCC V8.0: V8.0 Update 5 or later version as directed by Siemens.
  1. Until updates are applied, restrict access to the application webserver to trusted users only. Siemens identifies this as a specific mitigation.
  2. After updating, verify that affected web services run the fixed release for the applicable product branch and are not exposed beyond their operational need.
  3. Continue to apply network protection and secure-environment configuration recommended by Siemens. Do not treat a fix for one branch as evidence that parallel branches are fixed.

Detection

  1. Inventory systems running SIMATIC PCS 7, SIMATIC WinCC, or SIMATIC WinCC Runtime Professional, including the related web services.
  2. Determine whether WinCC WebNavigator, PCS 7 Web Server, or PCS 7 Web Diagnostics Server is installed, enabled, and reachable from untrusted networks.
  3. Compare deployed releases with Siemens' corresponding fixed baseline for the correct product branch. Do not assume that an update for one branch fixes another branch.
  4. Review available web server and network telemetry for unusual unauthenticated requests or responses containing account information. This is a precautionary review, not a Siemens-named IOC, and absence of log evidence does not prove safety.
  5. Check ACLs, firewalls, and reverse proxies to confirm that the application webserver is restricted to trusted users.